Fire extinguisher inspection checklist: the monthly check, the annual service and a log

Print a monthly fire extinguisher inspection checklist and log, with restaurant kitchen lines, and see what OSHA requires and what to do when one fails.

Start from the work orders template

Take requests, assign jobs, track them to done.

Use the template, free
On this page

A fire extinguisher inspection checklist is a monthly visual check of each extinguisher: it’s in its place, easy to reach, pin and seal intact, gauge in the green, and no damage. OSHA requires that check every month and a maintenance check every year. Most businesses hire a servicing company for the yearly one.

How we researched this: OSHA’s rule text and pages, plus state and city fire agency pages, checked November 2026.

It’s for the owner, office manager or facilities lead at a restaurant, shop, warehouse or property, whether you have 3 extinguishers or 60. Below: the checklist, what 29 CFR 1910.157 requires, what changes in a restaurant kitchen, who does what, and what to do when one fails. To track the monthly walk and each repair in one place, see the work order template. This isn’t legal advice; your local fire code and fire marshal decide.

What goes on a monthly fire extinguisher inspection checklist?

Print this page. Check every extinguisher against the lines below, tick its tag, then initial its box for the month in the grid (in Excel, add a row to the log). The lines are what you look at; the grid is what you write. A line you can’t tick is a defect. The sheet above is an example: one warehouse’s November log.

OSHA requires the monthly visual inspection (29 CFR 1910.157(e)(2)) but doesn’t list what to look at. These lines follow what the rule says an extinguisher must be: reachable, fully charged, operable and in its place. They also follow the self-inspection steps city fire programs publish, such as Portland’s.

CheckWrite it up if
☐ In its placeNot at its bracket or marked spot
☐ Visible and clear to reachAnything stacked, parked or hung in front; sign hidden
☐ Pin and tamper sealPin missing or seal broken
☐ Pressure gaugeNeedle outside the green, on units with a gauge
☐ FullFeels light, or weighs less than the label says
☐ BodyDents, rust, corrosion or leaks
☐ Hose and nozzleCracked, blocked or damaged
☐ InstructionsThe label facing out is missing or unreadable
☐ MountingBracket or hook loose, or the unit is on the floor
☐ Service tagMissing, or the annual date is over 12 months old
☐ K-class by cooking line (kitchens only)Missing, or not within reach of the fryers
☐ Hood system tag current (kitchens only)No tag, or the service date is over 6 months old
☐ Initial and date the tag, then the gridAlways

Where an extinguisher goes matters as much as its condition. OSHA sets travel distance: 75 feet or less to an extinguisher for Class A (ordinary combustibles) hazards, and 50 feet or less for Class B (flammable liquids). If someone would have to run past that, you have a gap to fix.

What’s different in a restaurant kitchen?

The cooking line adds two things a fire marshal looks for. Here’s what the Kansas State Fire Marshal’s hood suppression guidance, which draws on NFPA 96 (the standard most fire codes use for commercial cooking), says:

  • A K-class extinguisher by the fryers. K-class units are built for cooking oil and grease fires. Kansas says one shall be provided. Check it monthly with the rest and keep its yearly tag current.
  • The hood fire suppression system. That’s the pipes and nozzles over the fryers and grill, with a pull station. A certified firm services it at least every 6 months and updates the system’s own service tag. A current tag has a service date in the last 6 months. It’s a different tag from your extinguishers’.
  • Hood and duct cleaning is a third schedule, monthly to yearly depending on how much you cook. Your cleaning company sets it, and a clean hood doesn’t replace the suppression tag.

Other states and cities set their own rules, so ask your fire marshal which code they use. In a restaurant with turnover, name one person per shift to do the monthly walk and write their name in “Inspected by”.

Example: a taco shop’s monthly sheet starts like this.

  • FE-01 Fryer line, K-class: OK
  • FE-02 Back door: OK
  • FE-03 Dry storage: OK

How often do fire extinguishers need to be inspected, and by whom?

Four schedules. OSHA’s rule covers general industry; construction sites follow 29 CFR 1926.150. States with an OSHA-approved State Plan, and local fire codes, can add to it.

TaskHow oftenWho
Visual inspection (the checklist above)Every monthA trained person on your staff
Maintenance check, with the date recordedEvery yearUsually a servicing company
Empty and maintain stored pressure dry chemical unitsEvery 6 yearsUsually a servicing company
Hydrostatic pressure testEvery 5 or 12 years, by typeTrained people with test equipment

OSHA puts the duty on you: “the employer shall be responsible for the inspection, maintenance and testing” of every extinguisher ((e)(1)). It doesn’t say who does the monthly look, so you pick and train someone; Portland’s fire bureau names the owner or a responsible person. It doesn’t name who does the annual check either, though hydrostatic tests need trained people with suitable equipment. Some states go further: Utah bars any business from servicing portable extinguishers without a State Fire Marshal license. Check your state’s.

OSHA also requires training: an education program for employees at hire and at least yearly after, and yearly training for anyone your emergency plan says will use an extinguisher ((g)). Note the date in the log.

What does the annual maintenance and the tag cover?

OSHA says the employer “shall assure” every portable extinguisher gets an annual maintenance check, and that you record the date and keep the record for one year after the last entry or the life of the shell, whichever is less ((e)(3)). Stored pressure units don’t need an internal examination at that yearly visit.

In practice a servicing company walks the building, examines each unit, repairs or recharges it, and puts a tag on it showing the service date. The tag is the quickest record to check on a walk-through. Some states set what it must show, so ask your company what yours requires and whether it’s licensed where you are. Get a written list of every extinguisher serviced, by ID and location, and file it with your monthly sheets.

Book the annual visit for the same month every year, before the old tag turns 12 months old, not after.

When do 6-year maintenance and hydrostatic tests come due?

Most office, shop and warehouse units are stored pressure ABC dry chemical: an internal check every 6 years and a hydrostatic test (a pressure test of the cylinder) every 12. Read your label, and ask your service company which dates each of yours is on. Most fire codes adopt NFPA 10 for extinguishers; ask your fire marshal which code they use.

Common typeHydrostatic test
Stored pressure ABC dry chemical (most units)Every 12 years
Water or antifreezeEvery 5 years
Carbon dioxideEvery 5 years
Dry chemical, stainless steel shellEvery 5 years
Halon 1211 or 1301Every 12 years

That’s OSHA’s Table L-1, trimmed to common types. The 6-year step is for stored pressure dry chemical units that need the 12-year test ((e)(4)). Disposable, non-refillable units are exempt, and follow the maker’s label for their life. The 6-year clock restarts when a unit is recharged or tested. Test sooner if a unit shows new corrosion or damage, and a unit that fails comes out of the workplace. Keep each test certificate, with its date, the tester’s signature and the serial number, until the next test.

What do you do when a fire extinguisher fails inspection?

If you pull one, put another in its place that day and call your service company. OSHA requires equivalent protection while extinguishers are away for maintenance or recharging ((e)(5)).

  1. Check it now. Read the gauge and lift it. A missing pin and a broken seal mean someone may have pulled it, so don’t trust a unit that looks full.
  2. Pull it and tag it. Hang your own dated “Out of service” tag on it, so nobody takes it for a working one.
  3. Put another in its place. Same type, charged, that day. Write its ID on the sheet.
  4. Write it up as a work order. That’s a repair job with a priority, an owner and a due date. A unit that may be discharged is Urgent, due the same day.
  5. Have your service company recharge, repair or replace it. A unit that fails a hydrostatic test leaves the workplace.
  6. Log the return. Date it went back, who checked it, the new service tag.

What do a fire marshal and your insurer want to see?

Expect a fire marshal’s walk to touch four things: extinguishers where they should be and clear to reach, each one intact, a current service tag on each, and records showing the checks happened. Local rules decide the details, so ask your fire marshal’s office what theirs checks.

Have this ready in one folder:

  • The last 12 months of monthly logs. OSHA’s text doesn’t ask for a written record of the monthly check, but some fire departments, Portland’s for one, expect one on the tag or in a log. A year of initialed sheets is the easy answer.
  • Your annual service record, with the date. OSHA’s rule has you keep it one year after the last entry, or until the shell’s life ends, whichever comes first.
  • Hydrostatic test certificates for any unit tested.
  • Training dates.
  • A list of every extinguisher with its ID, location, type and serial number.

Your insurer may ask for the same. We found no insurer rule to quote, so ask your agent what your policy needs.

How do you keep a fire extinguisher inspection log?

Give every extinguisher a permanent ID, and put it on a label on the unit. Sort the log by building and location, so the monthly walk follows the route you’d naturally take. The download’s PDF has three pages: the checklist with a defects log, a 12-month grid with one row per extinguisher and a box of initials for each month, and a service-dates page with the last annual service, next annual due, 6-year and hydro dates. A site with 42 extinguishers prints two grid pages. The Excel file works out the next annual due date from the last service date.

If you want a fuller record per unit, our equipment maintenance log guide shows what one holds, the preventive maintenance checklist puts this check beside the rest of your building’s routine, and in a warehouse the forklift inspection checklist covers the daily check.

Keep extinguisher checks, defects and due dates in one place

FE-09’s missing pin was found at 9:10 and fixed by the next morning because the defect became a job with an owner and a due date. GoodTaco’s work order template does that part. Sign up free and you land in your own copy: add each building as a site and each extinguisher as equipment, with its serial number and install date.

  • A defect becomes a job. Staff send it from the request link, and urgent ones are due the same day.
  • The monthly walk repeats. A repeating job per building, every 1 month, is created 7 days before it’s due when someone on your team who can edit opens the app.
  • Each unit keeps its history. Open FE-09 and see every job against it.

Ask GoodTaco to make it yours:

Add Fire extinguisher to the equipment categories, a Type field (ABC, CO2, water, other), a Last annual service date and a Next annual due date on each piece of equipment, and an Out of service checkbox that shows on the board. Then add a Monthly check page where I pick a building and mark each extinguisher OK or Defect.

Already keep a list in a spreadsheet? Upload it and the records go into your app’s own built-in database.

GoodTaco is free to start. Paid plans start at $9 a month, and Pro at $49 a month includes 10 users; bigger teams talk to us about Enterprise.

Get every extinguisher checked, logged and ready for the fire marshal. Start free.

Frequently asked questions

How often do fire extinguishers need to be inspected?

OSHA's rule for general industry, 29 CFR 1910.157(e), requires a visual inspection every month and a maintenance check every year. Stored pressure dry chemical extinguishers that need a 12-year hydrostatic test are also emptied and maintained every 6 years. Hydrostatic tests come every 5 or 12 years, depending on the type. Local fire codes can add to this, so ask your fire marshal which code they use.

What should a monthly fire extinguisher inspection checklist include?

That the extinguisher is in its place and easy to see and reach, the pin and tamper seal are intact, the gauge needle is in the green, it feels full or weighs what the label says, the body has no dents, rust or leaks, the hose and nozzle are clear, the instructions face out, the bracket holds it, and the service tag is there and current. In a kitchen, add the K-class extinguisher by the cooking line and the hood system's service tag. Then initial the tag and log the unit.

Who can do a monthly fire extinguisher inspection?

OSHA makes the employer responsible for inspecting, maintaining and testing extinguishers but doesn't say who does the monthly visual check. In practice a trained person on your staff does it; Portland's fire bureau names the owner or a responsible person. The annual maintenance, the 6-year maintenance and hydrostatic tests are usually done by a servicing company. OSHA's text doesn't name who must do the annual check, but it requires trained persons with suitable equipment for hydrostatic tests, and some states, Utah for one, require servicing companies to be licensed.

Does OSHA require a written record of fire extinguisher inspections?

OSHA's text requires a record of the annual maintenance date, kept for one year after the last entry or the life of the shell, whichever is less. It doesn't spell out a written record of the monthly check, but some fire departments, Portland's for one, expect one on the tag or in a log. Hydrostatic test records, with the date, the tester's signature and the serial number, are kept until the next test.

What is the 6-year maintenance on a fire extinguisher?

Under 29 CFR 1910.157(e)(4), stored pressure dry chemical extinguishers that require a 12-year hydrostatic test are emptied and given the applicable maintenance procedures every 6 years. Disposable, non-refillable dry chemical units are exempt. The 6-year clock restarts when the unit is recharged or hydrostatically tested.

What do you do when a fire extinguisher fails inspection?

Pull it, tag it, and put another extinguisher in its place the same day, because OSHA requires equivalent protection while a unit is away for maintenance or recharging. Call your service company to repair, recharge or replace it, write the defect up as a job with an owner and a due date, and log the date it went back.

How often is a restaurant's hood fire suppression system serviced?

The Kansas State Fire Marshal's guidance says a hood suppression system must be serviced at least every 6 months by a certified firm, which updates the system's service tag, and that a Class K extinguisher must be provided. Other states and cities set their own rules, so ask your fire marshal.

What does a fire marshal check on fire extinguishers?

Marshals vary, but expect them to look for an extinguisher at each marked spot, clear access, an intact pin and seal, a gauge in the green, and a current service tag. Some will ask for your monthly log and your annual service record. Local rules and the fire marshal decide the details.

Free template

Start from the work orders template

Get your own copy of a working work orders app with sample records, ready to make yours. Free to start.

Use the template, free

Or turn your own sheet into an app

Keep exploring

Related guides and templates

View all articles

Guide

Marine repair software: what to track and what it costs

Marine repair software for boat shops: what to record on each boat, nine tools compared, eight with a listed price, and a year of work on northern water.

Guide

Vehicle inspection checklist: daily, DOT and forklift checks

Copy a daily vehicle inspection checklist and forklift pre-shift check, plus the DOT rules for DVIRs and annual inspections and what to do when an item fails.